THD (Total Harmonic Distortion)

See how far a PAN-42 device's current and voltage drift from a clean sine wave, right on your TimeView chart.

Written by Shir Goldstein

Updated at November 17th, 2026

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Getting Started
  • Dashboard
  • TimeView
    Get started Work with the chart Understand your data Time & comparison Save & share Advanced
  • Energy Apps
  • Alerts & Notifications
  • Reports
  • Administration & Settings
  • Partners
  • Import & Exports
  • Mobile App
    Getting Started & Signing In Navigating the App The Site Dashboard and Its Widgets TimeView Lite Events (Optimize + Event Management) Notifications, alerts & push Preferences, Support & App Behavior
  • Plans & Packages
  • Security & Certification
  • Deployment
  • Hardware Manuals
  • Datasheets & Specs
  • Frequently Asked Questions (FAQ)
    Bridge FAQs PAN-10/PAN-12/PAN-14 Sensors FAQs PAN-42 Sensor FAQs Software Platform FAQs Package FAQs
  • Legal
  • What’s New
  • Bidirectional-Power
  • Energy Star Portfolio Manager
  • Panoramic AI
+ More

Table of Contents

What Is THD? THD - Current vs. THD - Voltage Before You Start Where to Find It Reading THD on the Chart Comparing Periods Exporting THD Data How Accurate Is THD? Troubleshooting Related Articles

What Is THD?

What is it?

Mains power should be a smooth, clean wave. Some equipment distorts that wave, such as variable-speed drives, LED drivers and switching power supplies. THD (Total Harmonic Distortion) measures how much distortion there is.

Harmonics are extra, unwanted frequencies on top of the normal 50/60 Hz wave. The higher the THD, the more distorted the signal. High distortion can overheat transformers, make motors vibrate and interfere with sensitive equipment.

THD is a total. It combines all harmonics into one value. Individual harmonics (3rd, 5th and so on) aren't available.

Why use it?

  • Spot equipment that puts distorted current back onto your circuits, before it causes wear.
  • Tell a supply-side (grid) problem apart from a load-side (equipment) problem.
  • Track a site's power quality over time, next to the power and energy data you already chart.

THD - Current vs. THD - Voltage

THD comes as two separate series. You can turn on either one or both.

Series What it points to Guidance shown in the app
THD - Current The load: for example variable-speed drives, rectifiers or other non-linear loads drawing distorted current. Most reliable at high distortion. Small values may be approximate.
THD - Voltage The supply: a grid or feed-quality issue affecting everything on that circuit. Indicative. Best for trend, most reliable when distortion is high.

Non-linear load: equipment that draws current in pulses instead of a smooth wave, such as drives, rectifiers and power supplies.


Before You Start

What you'll need:

  • A PAN-42 meter. THD is measured by the PAN-42 meter itself. Other Panoramic Power sensors don't report it.
  • Firmware version 2. Only PAN-42 meters on firmware version 2 (shown as 2.04, 2.05 and so on) report THD. To check, go to Inventory → Panoramic Sensors and look at the Firmware version column. If it starts with 0 or 1, the meter doesn't report THD. You can still turn THD on, but the chart stays empty.
  • A line chart. Select a PAN-42 circuit or device. THD works whatever the chart is showing: Power, Current or Voltage.

If you need THD on an older meter, contact your Panoramic Power contact, or submit a ticket to the PowerRadar team and we'll get back to you.


Where to Find It

You can turn on THD in two places.

For all PAN-42 devices on the chart

  1. Click Add-ons in the TimeView toolbar.
  2. Under the Quality group, check THD - Current and/or THD - Voltage.

When add-ons are on, the button shows how many, for example Add-ons 2.

For a single device

  1. In the Legend on the right, hover over the device row and click the add-ons icon.
  2. In the Chart series add-ons panel, open the Quality category.
  3. Check THD - Current and/or THD - Voltage. This affects only that device.

Note: If a THD row is greyed out, hover over it to see what's missing.

First-time explanation

The first time you turn on THD (or Sag & Swell events), a window called About PAN-42 power quality explains what the data is and its accuracy limits. It appears once per user. Closing it doesn't turn the add-on off.


Reading THD on the Chart

Once THD is on, each series shows up as:

  • A dashed line over time, for each THD series you turned on.
  • A shared right-side Y-axis, with values in percent (for example 5 %, 10 %, 15 %). Both THD lines use the same axis.
  • A row under the device in the Legend, inside a collapsible Quality group, labelled THD - Current or THD - Voltage with a % unit tag. The group shows how many add-ons are on, for example Quality (2).
  • A value in the hover tooltip, shown as the device name followed by the series, for example Main Panel (THD - Current) 12.75 %.

Device or circuit

  • For a device, the THD line is the average of its three phases.
  • For a circuit, the THD line is that phase.

Notes:

  • A gap means no reading. The THD line and tooltip row appear only when the meter sent a THD reading. PowerRadar doesn't fill gaps with 0%. A missing value never means zero distortion.
  • Values above 100% are possible. On heavily distorted circuits the harmonic content can be larger than the 50/60 Hz wave itself. If you see sustained very high readings on a normal site, contact the PowerRadar team.

Comparing Periods

THD works with Compare, in both views:

  • Overlay view: the THD lines for both periods are drawn on the same chart. The Legend shows a Current and a Compared line style under each THD series.
  • Split view: each period gets its own chart, and each chart shows its own THD lines.

The hover tooltip shows the THD value for both periods side by side, with the percentage change between them.


Exporting THD Data

Manual Export

Choose THD - Current (%) or THD - Voltage (%) as the measurement type.

Scheduled exports (Auto-export)

In a Pan-42 Measurements export job, check Include power quality columns. Each row then includes current_thd(%) and voltage_thd(%), along with the Sag & Swell columns. The column names are the same in CSV and JSON.

A THD value of zero is left blank, because a 0 means no reading, not zero distortion.


How Accurate Is THD?

THD is a real-time measurement from the PAN-42 meter, not a lab-grade instrument reading. Keep this in mind:

  • THD - Current is reliable when distortion is significant, roughly above 15–20%. Below that, the meter has a measurement floor of about 5%, so small values may read higher than the true value. Treat a low reading as approximate.
  • THD - Voltage is indicative. It tends to slightly under-report low distortion and is accurate when distortion is high. Use it to spot trends.
  • Use both for trend and diagnosis, not for compliance or billing-grade measurement.

How load affects THD - Current

Current on the circuit What to expect
Under about 2 A No reading. The line has a gap.
About 2–20 A Readings come and go. Treat them as unreliable.
About 20 A and above Readings are usually there. An occasional gap is normal.

Notes:

  • Occasional THD - Voltage gaps are normal. Some voltage THD readings drop out. This isn't a fault with the meter.
  • Light loads mean fewer readings. Each 15-minute or hourly value averages only the readings that arrived. On a lightly loaded circuit, a value may rest on only a few readings, so treat it as indicative.

Troubleshooting

  • Symptom: THD is on, but the chart shows no THD line at all. Fix: Check the meter's firmware under Inventory → Panoramic Sensors. If the Firmware version starts with 0 or 1, the meter doesn't report THD. Contact your Panoramic Power contact, or submit a ticket to the PowerRadar team.
  • Symptom: The THD - Current line has many gaps. Fix: Check the current on the circuit. Below about 20 A, gaps are expected. 
  • Symptom: The THD rows are greyed out in the Add-ons menu. Fix: Select a PAN-42 circuit or device on a line chart. Hover over the greyed-out row to see what's missing.

Related Articles

  • Sag & Swell Events
  • Chart Series Add-ons & PAN-42 Metrics
  • Why PAN-42?
  • Export Jobs: Pan-42 Measurements Interface
thd harmonics distortion timeview total harmonic distortion quality add-ons pan-42 current thd voltage thd