If a potential transformer is required, what specifications are required? Are there any recommended ones to use?

Written by Maggie Fashbaugh

Updated at May 1st, 2025

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Using the Platform
    Getting Started Administration Energy Applications Triggers and Notification Center Data Export Data Import Reports
  • Hardware & Deployment
    Frequently Asked Questions (FAQ) Hardware Datasheets and Deployment Guides Software Deployment Guide Troubleshooting Flow Charts
  • Interactive Demos
  • Legal
+ More

When connecting the PAN-42 sensor to a panel with phase-neutral voltages over 277VAC / 480V (such as 346/600VAC systems in Canada), it is necessary to use potential transformers (PTs) at the voltage inputs.


PTs must be chosen so that their output (secondary) voltage is always within PAN-42’s input voltage range (110-277VAC phase-neutral). It is recommended to use PTs with high voltage accuracy and minimal phase shift, in order to minimize the effect on PAN-42 measurement accuracy.


For Canadian 346/600VAC systems, it is recommended to use PTs with 346VAC inputs and 120VAC outputs, such as the following models:
• Instrument Transformers (ITI/GE) model 3VT468-346 (3-phase)
• Hammond Manufacturing model VT56A (1-phase)
• For noisy industrial environments, where voltage spikes are common: Hammond Power Solutions model PH50MGJ (1-phase) – connect to 380V input, 120V output

Note: The above PTs are recommended for use with the PAN-42 sensor, but they are not considered a part of the PAN-42 product, and Panoramic Power does not take responsibility for their certification status or suitability to the installation site.

 

 

potential transformer specifications