What is the distance range of the Bridge and the sensors?
- Getting Started
- Dashboard
- TimeView
- Energy Apps
- Alerts & Notifications
- Reports
- Administration & Settings
- Partners
- Import & Exports
- Mobile App
- Plans & Packages
- Security & Certification
- Deployment
- Hardware Manuals
- Datasheets & Specs
- Frequently Asked Questions (FAQ)
- Legal
- What’s New
- Bidirectional-power
If there was nothing between the Bridge and the sensors, the distance can be as far as 40 feet / 12 meters.
But because the sensors are usually installed in electrical panels and are made of metal (an RF interfering material), we recommend installing Bridges no farther than 20 feet / 6 meters away from the sensors.
However, the RSSI should always be the key indicator of how close/far the Bridge is installed from the sensors. An acceptable RSSI range is -30 dBm and -75 dBm.
Given this ideal range, there is also a minimum distance recommended, especially for PAN-42 meter installation as if the RSSI is too strong between the Bridge and the sensors, the data delivery will be inconsistent. Ensure the Bridge is installed at least 3 feet / 1 meter away from PAN-42 sensors.